Unit Specifications
Common Characteristics:
|
Warranty:
|
25 Years Unlimited Free
Replacement
|
|
Manufacturer
Qualification:
|
ISO-9001
|
|
Unit
Listings:
|
UL 1449 Second Edition,
CUL
|
|
Enclosure:
|
Steel, NEMA 12
|
|
Mounting:
|
Conduit fitting (internally
threaded) and external mounting feet.
|
|
Connection
Method:
|
#10 stranded wire.
|
|
Circuit
Design:
|
Parallel connected,
hybrid circuit design incorporating all mode protection (10 modes for 3
phase wye units). All protection circuits are completely encapsulated in
our exclusive compound to assure long component life and complete protection
from the environment and/or vibration.
|
|
Protection
Modes:
|
Dedicated protection
components and circuitry for each mode. Discrete L-N, L-L (Normal Mode),
and Discrete L-G, N-G (Common Mode). 10 modes / 3 phase wye system.
|
|
Input
Power Frequency:
|
50-420Hz (60Hz typical)
|
|
Response
Time:
|
Less than 1 nanosecond
|
|
Circuit
Diagnostics:
|
Super Bright LED, 1
per phase, normally on.
|
Measured Limiting
Voltage Performance and Electrical Specifications
|
Model
|
Circuit Type
|
MCOV*
|
Mode
|
UL Suppressed Voltage
Rating
|
|
xxx1P1
|
120V, Single Phase
(2 wire + ground)
|
150 L-N
150 L-G
150 N-G
|
L-N
L-G
N-G
|
Less than 330V
Less than 330V
Less than 330V
|
|
xxx1S1
|
120/240V, Split Phase
(3 wire + ground)
|
300 L-L
150 L-N
150 L-G
150 N-G
|
L-L
L-N
L-G
N-G
|
Less than 600V
Less than 330V
Less than 330V
Less than 330V
|
|
xxx3Y1
|
120/208V, 3 Phase wye
(4 wire + ground)
|
300 L-L
150 L-N
150 L-G
150 N-G
|
L-L
L-N
L-G
N-G
|
Less than 600V
Less than 330V
Less than 330V
Less than 330V
|
|
xxx3Y2
|
277/480V, 3 Phase wye
(4 wire + ground)
|
550 L-L
320 L-N
320 L-G
320 N-G
|
L-L
L-N
L-G
N-G
|
Less than 1500V
Less than 800V
Less than 800V
Less than 800V
|
|
xxx3N2
|
240V, 3 Phase Delta
(3 wire + ground)
|
320 L-L
320 L-G
|
L-L
L-G
|
Less than 800V
Less than 800V
|
|
xxx3N4
|
480V, 3 Phase Delta
(3 wire + ground)
|
550 L-L
550 L-G
|
L-L
L-G
|
Less than 1500V
Less than 1500V
|
xxx = Series rating
(i.e. "SDL", CDL", "SIL", "CIL", "SHL", "CHL", "SHDL").
* Note: Devices listed with
150V MCOV are available with 130V MCOV option. To exercise this option
add the suffix "T" to the model number. (Example SDL3Y1-T)
OPTIONS
|
Enhanced
Sinewave Tracking Circuitry:TM
|
Some leakage current
is present on the N-G mode due to EST circuitry. If this is a concern in
your application, please add the suffix "N" as the last digit of the order
number. This will eliminate the N-G mode in the EST circuitry. Example:
CDL3Y1-N
|
|
Integral
Fusing:
|
Requires no circuit
interrupt external of the surge suppression device. Order indicator "F"
following the base unit model number. Example: SDL3Y1-F
|
|